106 H7 ASD Operation Manual
Jump Frequency #2 Bandwidth
Program
Special Control Parameters
Jump Frequencies
This parameter establishes a plus-or-minus value for Jump Frequency #2
(F272).
Direct Access Number F273
Parameter TypeNumerical
Factory Default0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 30.0
Units — Hz
Jump Frequency #3
Program
Special Control Parameters
Jump Frequencies
Same as Jump Frequency #1 (F270) and is used when multiple frequencies are
to be jumped (see the plus-or-minus value setting at F275). When multiple
jump frequencies overlap, the system will recognize the lowest and the highest
frequencies as one jump range.
Direct Access Number F274
Parameter TypeNumerical
Factory Default0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Jump Frequency #3 Bandwidth
Program
Special Control Parameters
Jump Frequencies
This parameter establishes a plus-or-minus value for Jump Frequency #3
(F274).
Direct Access Number F275
Parameter TypeNumerical
Factory Default0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 30.0
Units — Hz
Jump Frequency Processing
Program
Special Control Parameters
Jump Frequencies
Jump
Frequency Processing
This parameter determines if the output frequency of the ASD or the PID
feedback signal will be used as a reference for determining the Jump
Frequency range.
See F270 for further information on the Jump Frequency settings.
Settings:
Process Amount (use PID feedback)
Output Frequency
Direct Access Number F276
Parameter TypeSelection List
Factory DefaultProcess Amount
Changeable During Run — Yes
F273 F276