H7 ASD Operation Manual 111
Supply Voltage Compensation
Program
Protection Parameters
Base Frequency Voltage
This parameter Enables/Disables the Voltage Compensation function. This
function provides an output waveform adjustment that compensates for changes
in the input voltage.
Direct Access Number F307
Parameter Type Check Box
Factory Default Enabled
Changeable During Run — No
Dynamic Braking Resistance
Program
Protection Parameters
Dynamic Braking
This parameter is used to input the resistive value of the Dynamic Braking
Resistor if so equipped.
For additional information on selecting the proper resistance value for a given
application contact Toshiba’s Marketing Department.
Note: Using a resistor value that is too low may result in system damage.
Direct Access Number F308
Parameter Type Numerical
Factory Default — (drive dependent)
Changeable During Run — No
Minimum — 1.0
Maximum — 1000.0
Units —
Dynamic Braking Resistance Capacity
Program
Protection Parameters
Dynamic Braking
This parameter is used to input the wattage of the Dynamic Braking Resistor
if so equipped.
For additional information on selecting the proper resistor wattage value for a
given application contact Toshiba’s Marketing Department.
Note: Using a resistor with a wattage rating that is too low may result in
system damage.
Direct Access Number F309
Parameter Type Numerical
Factory Default — (drive dependent)
Changeable During Run — No
Minimum — 0.01
Maximum — 600.0
Units — kW
Ridethrough Time
Program
Protection Parameters
Retry/Restart
In the event of a momentary power outage, this parameter determines the length
of the Ridethrough time. During a Ridethrough, regenerative energy is used
to maintain the control circuitry settings; it is not used to drive the motor.
The Ridethrough will be maintained for the number of seconds set using this
parameter.
Note: The actual Ridethrough Time is load-dependent.
Direct Access Number F310
Parameter Type Numerical
Factory Default 2.00
Changeable During Run — Ye s
Minimum — 0.00
Maximum — 320.0
Units — Seconds
Disable Forward Run/Disable Reverse Run
Program
Frequency Setting Parameters
Forward/Reverse
Disable
This parameter Enables/Disables the Forward Run or Reverse Run mode.
If either direction is disabled, commands received for the disabled direction will
not be recognized. If both directions are disabled, the received direction
command will determine the direction of the motor rotation.
Direct Access Number F311
Parameter Type Check Box
Factory Default Disabled
Changeable During Run — No
F307 F311
www . ElectricalPartManuals . com