H7 ASD Operation Manual 171
Communications Reference Setpoint #2 (%)
Program
Communication Setting Parameters
Communication
Reference Adjust
This parameter is used to set the gain and bias of the Communications
Reference speed control input.
See F811 for further information on this setting.
This parameter sets the Communications Reference input value that represents
Communications Reference Speed Setpoint #2 (frequency). This value is
entered as 0 to 100% of the Communications Reference input value range.
Direct Access Number F813
Parameter Type Numerical
Factory Default 100.0
Changeable During Run — Ye s
Minimum — 0.00
Maximum — 100.0
Units — %
Communications Speed Setpoint #2 (frequency)
Program
Communication Setting Parameters
Communication
Reference Adjust
This parameter is used to set the gain and bias of the Communications
Reference speed control input.
See F811 for further information on this setting.
This parameter sets the Communications Reference Speed Setpoint #2.
Direct Access Number F814
Parameter Type Numerical
Factory Default 80.0
Changeable During Run — Ye s
Minimum — 0.0
Maximum — Max. Freq. (F011)
Units — Hz
RS485 Baud Rate
Program
Communication Setting Parameters
Communication
Settings
This parameter sets the RS485 baud rate.
Settings:
1200
2400
4800
9600
19200
38400
Direct Access Number F820
Parameter Type Selection List
Factory Default 9600
Changeable During Run — Ye s
RS485 Wire Count
Program
Communication Setting Parameters
Communication
Settings
This parameter sets the communications protocol to the 2 or 4 wire method.
Settings:
2 wire
4 wire
Direct Access Number F821
Parameter Type Selection List
Factory Default — 4
Changeable During Run — Ye s
F813 F821