H7 ASD Operation Manual 85
VI/II Speed Reference Setpoint #1 (frequency)
Program
Frequency Setting Parameters
Speed Reference
Setpoints
VI/II
This parameter is used to set the gain and bias of the VI/II input terminals when
either terminal is used as the control input while operating in the Speed
Control mode.
See F201 for further information on this setting.
This parameter sets VI/II Speed Reference Setpoint #1 (frequency) and is the
frequency that is associated with the setting of F201.
Direct Access Number F202
Parameter TypeNumerical
Factory Default0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq. (F011)
Units — Hz
VI/II Speed Reference Setpoint #2 (%)
Program
Frequency Setting Parameters
Speed Reference
Setpoints
VI/II
This parameter is used to set the gain and bias of the VI/II input terminals when
either terminal is used as the control input while operating in the Speed
Control or the Torque Control mode.
See F201 for further information on this setting.
This parameter sets the VI/II input level that represents Reference Setpoint #2
(torque or frequency). This value is entered as 0 – 100% of the VI/II input
signal range.
Direct Access Number F203
Parameter TypeNumerical
Factory Default100.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Units — %
VI/II Speed Reference Setpoint #2 (frequency)
Program
Frequency Setting Parameters
Speed Reference
Setpoints
VI/II
This parameter is used to set the gain and bias of the VI/II input terminals when
either terminal is used as the control input while operating in the Speed
Control mode.
See F201 for further information on this setting.
This parameter sets VI/II Speed Reference Setpoint #2 (frequency) and is the
frequency that is associated with the setting of F203.
Direct Access Number F204
Parameter TypeNumerical
Factory Default80.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq. (F011)
Units — Hz
VI/II Torque Reference Setpoint #1 (%)
Program
Torque Setting Parameters
Setpoints
VI/II
This parameter is used to set the gain and bias of the VI/II input terminals when
either terminal is used as the control input while operating in the Torque
Control mode.
This is accomplished by establishing an associated V/f output pattern for a
given VI/II input level and motor load.
See F201 for further information on this setting.
This parameter sets Torque Reference Setpoint #1 (%) and is the output
torque value that is associated with the setting of F201. This value is entered as
0 to 250% of the rated torque.
Direct Access Number F205
Parameter TypeNumerical
Factory Default0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 250.0
Units — %
F202 F205
www . ElectricalPartManuals . com