– 104 –
7. HYDRO UNIT INSTALLATION MANUAL
Engineering Data Book
7
Electrical supply/cable specifications
▼ Wiring specifications
▼ Wiring specifications (control line)
Description
Model name
HWS-
POWER
SUPPLY
Maximum
current
Installation
fuse rating
Power wire Connection destination
Outdoor
unit
power
Power
input
1403H-E
220-230 V ~
50 Hz
22.8A 25 A 2.5 mm² or more
, 1103H-E
220-230 V ~
50 Hz
22.8A 25 A 2.5 mm² or more
803H-E
220-230 V ~
50 Hz
19.2A 20A 2.5 mm² or more
1603H8-E,
1603H8R-E
380-400V 3N~
50Hz
14.6A 16A 2.5 mm² or more
, ,
,
1403H8-E,
1403H8R-E
380-400V 3N~
50Hz
14.6A 16A 2.5 mm² or more
1103H8-E,
1103H8R-E
380-400V 3N~
50Hz
14.6A 16A 2.5 mm² or more
Hydro
inlet
heater
power
Power
input for
backup
heater
1403XWHM3-E
220-230V ~
50Hz
13A 16A 1.5 mm² or more ,
TB02
1403XWHD6-E
220-230V 3~
50Hz
23A 25A 2.5 mm² or more , ,
1403XWHT6-E
380-400V 3N~
50Hz
13A(13A x 2P) 16A 1.5 mm² or more
, ,
,
1403XWHT9-E
380-400V 3N~
50Hz
13A(13A x 3P) 16A 1.5 mm² or more
803XWHM3-E
220-230V ~
50Hz
13A 16A 1.5 mm² or more ,
803XWHD6-E
220-230V 3~
50Hz
23A 25A 2.5 mm² or more , ,
803XWHT6-E
380-400V 3N~
50Hz
13A(13A x 2P) 16A 1.5 mm² or more
, ,
,
803XWHT9-E
380-400V 3N~
50Hz
13A(13A x 3P) 16A 1.5 mm² or more
Power input for cylinder
heater
220-230V ~
50Hz
12A 16A 1.5 mm² or more , TB03
Outdoor-Hydro unit Connection 1.5 mm² or more , ,
Hydro -Cylinder Connection 1.5 mm² or more , TB03
Description Line spec
Maximum
current
Maximum length
Connection
destination
3-way valve control 2 line or 3 line 100 mA 12 m 0.75 mm² or more
, ,
(TB05)
2-way valve control 2 line 100 mA 12 m 0.75 mm² or more , (TB05)
Mixing valve control 3 line 100 mA 12 m 0.75 mm² or more
, ,
or
, ,
(TB04)
2-zone thermo sensor 2 line 100 mA 5 m 0.75 mm² or more , (TB06)
Cylinder thermo sensor
2+GND(shielded
wire)
100 mA 5 m 0.75 mm² or more , (TB06)
Second remote controller 2 line 50 mA 50 m 0.5 mm² or more , (TB07)