2.SYSTEM OVERVIEW
Engineering Data book
7
2-1. System Combination
Combination
2-2. Hydro Unit
80 class
112,140,160 class
Outdoor Unit
Hydro Unit
HWS-
803H-E
HWS-
1103H-E
HWS-
1403H-E
HWS-
1103H8-E
HWS-
1403H8-E
HWS-
1603H8-E
HWS-
1103H8R-E
HWS-
1403H8R-E
HWS-
1603H8R-E
Backup
heater
HWS-803XWHM3-E
z
––––––––~, 3kW
HWS-803XWHT6-E
z
––––––––3N ~, 6kW
HWS-803XWHD6-E
z
––––––––3~, 6kW
HWS-803XWHT9-E
z
–– –––––3N~, 9kW
HWS-1403XWHM3-E
z z z z z z z z
~, 3kW
HWS-1403XWHT6-E
z z z z z z z z
3N~, 6kW
HWS-1403XWHD6-E
z z
––––––3~, 6kW
HWS-1403XWHT9-E
z z z z z z z z
3N~, 9kW
Single phase model 3 phase model 3 phase with bottom plate heater
Hot water cylinder
HWS-1501
CSHM3-E
HWS-2101
CSHM3-E
HWS-3001
CSHM3-E
HWS-1501
CSHM3-UK
HWS-2101
CSHM3-UK
HWS-3001
CSHM3-UK
Hydro unit
HWS-803XWHM3-E
z
HWS-803XWHT6-E
HWS-803XWHD6-E
HWS-803XWHT9-E
HWS-1403XWHM3-E
HWS-1403XWHT6-E
HWS-1403XWHD6-E
HWS-1403XWHT9-E
Hydro Unit HWS-803XWHM3-E HWS-803XWHT6-E
HWS-803XWHD6-E
HWS-803XWHT9-E
Back up heater capacity 3.0 6.0 9.0
Power supply
for back up heater 220-230V ~ 50Hz 380-400V 3N~ 50Hz 220-230V 3~ 50Hz 380-400V 3N~ 50Hz
for hot water cylinder heater
(option)
220-230V ~ 50Hz
Leaving water
temperature
Heating (°C) 20-55
Cooling (°C) 10-25
Hydro Unit HWS-1403XWHM3-E HWS-1403XWHT6-E
HWS-1403XWHD6-E
HWS-1403XWHT9-E
Back up heater capacity 3.0 6.0 9.0
Power supply
for back up heater 220-230V ~ 50Hz 380-400V 3N~ 50Hz 220-230V 3~ 50Hz 380-400V 3N~ 50Hz
for hot water cylinder heater
(option)
220-230V ~ 50Hz
Leaving water
temperature
Heating (°C) 20-55
Cooling (°C) 10-25