8
Outdoor Units: HWS-1103H8(R)-E, HWS-1403H8(R)-E, HWS-1603H8(R)-E
Hydro Units:
HWS-1403XWH**-E
Water Piping
WARNING
• Install water pipes according to the regulations of respective countries.
• Install water pipes in a freeze-free place.
• Make sure that water pipes have sufficient pressure resistance
(The setting value of the pressure relief valve is 0.3 MPa).
CAUTION
• Do not use zinc plated water pipes. When steel pipes are used, insulate both ends of the pipes.
• The water to be used must meet the water quality standards specified in EN directive 98/83 EC.
Water Circuit
Install a strainer with 30 to 40 meshes (procure locally) at
the water inlet of the Hydro Unit.
Install drain cocks (procure locally) for water charge and
discharge at the lower part of the Hydro Unit.
Make the piping route a closed circuit. (An open circuit may
cause a failure).