4.HYDRO UNIT
Engineering Data book
22
4
4-4-3. Control line
4-4-4. External Device
Electrical connection for external booster heater
TB04
A
B
C
D
1
2
3
4
5
6
A
B
1
2
3
4
1
2
3
4
1
2
3
4
TB05
PJ20
PJ20
TB06
CN208
OPTION OPTION
CN209
7
8
9
1
2
3
4
TB04
CW
CCW
N
Mixing-Valve
type 2 for 2 zone
control
Max 12 m
230 V 100 mA
0.75 mm² or more
Mixing-Valve type 1
for 2 zone control
Max 5 m shield wire 0.75
mm² or more
Temp sensor in hot
water cylinder
Max 12 m
230 V 1 A
0.75 mm² or more
Pump (local)
Max 12 m
230 V 100 mA
0.75 mm² or more
Booster heater
(local)
Max 12 m
230 V 1 A
0.75 mm² or more
Alert output
(local)
Boiler operation
(local)
Defrost output
(local)
Compressor
Operation output
(local)
Max 12 m
non voltage
0.75 mm² or more
Temp sensor for
2 zone control
Max 5 m shield
wire 0.75 mm² or
more
2Way-Valve
for cooling
stop
3Way-Valve for hot
water cylinder
1234567 8 9
Terminal Block 05
Booster Heater