–93–
7. HYDRO UNIT INSTALLATION MANUAL
Engineering Data Book
8 START UP AND CONFIGURATION
Set the DIP switches and function codes.
Setting DIP Switches on the Board in the Hydro Unit
Detach the front cover and the electric parts box cover of the Hydro Unit.
Set the DIP switches on the main board.
SW10 Description
Switch mode
Default setting
3 External P2 pump operation Continuous operation OFF ON
Interlocked with the
internal pump
synchronized with P1.
SW11 Description
Switch mode
Default setting
1 Internal backup heater operation Operate OFF ON Not operate
2 Hot water cylinder heater operation Operate OFF ON Not operate
3 Booster heater operation Operate OFF ON Not operate
SW12 Description
Switch mode
Default setting
1 Hot water supply operation Valid OFF ON Invalid
2 Zone 1 operation Valid OFF ON Invalid
3 Zone 2 operation Invalid OFF ON Valid
SW13 Description
Switch mode
Default setting
1 Type of motorized 3-way valve
2-wire spring return type
3-wire SPST type
OFF ON 3-wire SPDT type
2 Interlocking with boiler Invalid OFF ON Valid
3 Auto restart for power failure Auto restart OFF ON Manual restart
4–
SW02 Description Default setting
4 Room thermostat Invalid OFF ON Valid
ON
OFF
SW10 SW11 SW12 SW13
1
2
3
4
ON
1
2
3
4
ON
1
2
3
4
ON
1
2
3
4
ON
Fig. 8-01