7. HYDRO UNIT INSTALLATION MANUAL
Engineering Data Book
7
Electrical Installation
WARNING
Ensure electrical circuits are isolated before commencing the electrical installation.
The electrical installation must be completed by a qualified electrician.
The electrical installation must comply to all Local, National and International electrical installation regulations.
This product must be earthed in accordance with Local, National and International electrical installation regulations.
CAUTION
The Hydro Unit must be connected to a dedicated power supply for the back up heater circuit.
The electrical supply must be protected by a suitably sized over current protection device (fuse, MCB etc) and an
earth leakage protection device.
The Hydro Unit must be connected to the mains power supply using a isolating switch which disconnects all poles
and has a contact separation of at least 3 mm.
The cord clamps, attached to the Hydro Unit, must be used to secure the electrical cables.
Wrong connection of electrical cables may result in electrical component failure or fire.
Ensure the electrical cables are sized in accordance with the installation instructions.
Power line
1
2
3
1
2
3
1
2
1
2
L
N
L
N
TB03
TB01
L
N
TB02 TB02
N
L1
L1
L3
L2
Backup heater
230 V ~ (3 kW type)
Backup heater
400 V 3N ~ (6.9 kW type)
Input power
230 V ~
50 Hz
Input power
400 V 3N ~
50 Hz
Leakage
breaker 30 mA
Leakage
breaker 30 mA
Hot water cylinder
Input power for
cylinder heater
230 V ~ 50 Hz
Leakage
breaker
30 mA
Hydro unitOutdoor unit
Leakage
breaker
30 mA
Input power
230 V ~
50 Hz
Fig. 7-19
20-EN