4
Average heating capacity and power input
* Heating capacity and power input are include defrost cycle data.
* Heating capacity and power input are shown at maximum compressor operating frequency
* Power input does not include water pump power.
* Heating capacity and power input are measured in accordance with EN14511.
Capacity (kW)
LWT (°C)
30 35 40 45 50 55
TO
(°C)
-20 3.93 3.83 3.74 — — —
-15 4.66 4.54 4.44 — — —
-7 5.45 5.30 5.15 4.99 — —
-2 6.24 6.11 5.97 5.84 5.69 —
2 6.86 6.75 6.64 6.52 6.47 6.38
7 9.02 8.78 8.58 8.34 8.11 7.87
10 9.56 9.29 9.10 8.84 8.42 8.29
12 10.11 9.81 9.62 9.35 8.92 8.87
15 10.94 10.60 10.41 10.13 9.68 9.52
20 12.42 11.99 11.82 11.50 11.03 10.78
Power input (kW)
LWT (°C)
30 35 40 45 50 55
TO
(°C)
-20 1.70 1.82 1.90 — — —
-15 1.78 1.90 2.00 — — —
-7 2.06 2.21 2.33 2.47 — —
-2 2.10 2.26 2.39 2.56 2.86 —
2 2.11 2.28 2.43 2.60 2.88 3.17
7 1.87 2.07 2.25 2.46 2.65 2.85
10 1.84 2.03 2.21 2.42 2.61 2.86
12 1.83 2.02 2.20 2.41 2.60 2.87
15 1.83 2.02 2.20 2.41 2.60 2.88
20 1.82 2.01 2.18 2.44 2.58 2.91
COP
LWT (°C)
30 35 40 45 50 55
TO
(°C)
-20 2.31 2.10 1.97 — — —
-15 2.62 2.39 2.22 — — —
-7 2.65 2.40 2.21 2.02 — —
-2 2.97 2.70 2.50 2.28 1.99 —
2 3.25 2.96 2.73 2.51 2.25 2.02
7 4.82 4.24 3.81 3.39 3.06 2.76
10 5.20 4.58 4.12 3.65 3.23 2.90
12 5.52 4.86 4.37 3.88 3.43 3.09
15 5.98 5.25 4.73 4.20 3.72 3.31
20 6.82 5.97 5.42 4.71 4.28 3.70
TO : Outdoor temperature (DB°C) RH85%
LWT : Leaving water temperature (°C)