Outdoor Unit
Installation Manual
– 6 –
2 Accessory parts
Part name
Qty
Shape Usage
HWT-
40,60
HWT-
80,110,140
Outdoor Unit installation manual 1 1 Hand this directly to the customer.
Drain nipple * 1 1
Waterproof rubber cap A * - 4
Waterproof rubber cap A
Waterproof rubber cap B * 2 1
Waterproof rubber cap B
Protective bush - 1 For protecting wires (pipe cover)
Guard material for passage part - 1
For protecting passage part (pipe
cover)
Energy label 1 1
Product che 1 1
WEEE Manual
WEEE : Waste electrical and
electronic equipment
1 1
F-Gas label 1 1
Protection sheet 1 1
Cable tie - 4
* (HWT-80*H(8)RW-E, HWT-110*H(8)RW-E, HWT- 140*H(8)RW-E) are not eligible.
3 Installation of R32 Air to Water Heat Pump
CAUTION
R32 refrigerant Air to Water Heat Pump installation
• ThisAirtoWaterHeatPumpadoptstheHFCrefrigerant(R32)whichdoesnotdestroyozonelayer.
Therefore, during installation work, make sure that water, dust, former refrigerant, or refrigerant oil does not enter
the R32 refrigerant Air to Water Heat Pump cycle. To prevent mixing of refrigerant or refrigerant oil, the sizes of
connecting sections of charge port on the main unit and installation tools are different from those of the conven-
tional refrigerant units.
Accordingly, special tools are required for the R32 or R410A refrigerant units. For connecting pipes, use new and clean
piping materials with high pressure fittings made for the R32 or R410A only, so that water and/or dust does not enter.
• Whenusingexistingpiping,referto“15APPENDIX-[1]Existingpiping”.
Required Tools/Equipment and Precautions for Use
Prepare the tools and equipment listed in the following table before starting the installation work.
Newly prepared tools and equipment must be used exclusively.
Legend
: Conventional tools (R32 or R410A)
: Prepared newly (Use for R32 only)
Tools / equipment Use Howtousetools/equipment
Gauge manifold
Vacuuming / charging
refrigerant and operation check
Conventional tools (R32 or R410A)
Charging hose
Conventional tools (R32 or R410A)
Charging cylinder Can not be used
Unusable (Use the electronic refrigerant charging
scale)
Gas leak detector Charging refrigerant
Conventional tools (R32 or R410A)
Vacuum pump Vacuum drying
Conventional tools (R32 or R410A)
Usable if the backow prevention adapter is installed.
Vacuum pump with backow
prevention function
Vacuum drying
Conventional tools (R32 or R410A)
Flare tool Flare machining of pipes
Conventional tools (R32 or R410A)
Bender Bending pipes
Conventional tools (R32 or R410A)
Refrigerant recovery equipment Refrigerant recovery
Conventional tools (R32 or R410A)
Torque wrench Tightening are nuts
Conventional tools (R32 or R410A)
Pipe cutter Cutting pipes
Conventional tools (R32 or R410A)
Refrigerant cylinder Charging refrigerant
Prepared newly (Use for R32 only)
Welding machine and nitrogen
cylinder
Welding pipes
Conventional tools (R32 or R410A)
Electronic refrigerant charging
scale
Charging refrigerant
Conventional tools (R32 or R410A)
11-EN
12-EN