166
11. Night time Low-noise Setting
This function is available only for the header remote controller.
This setting is used to reduce noise output, from the outdoor unit, during night time for neighbors. Night time low-
noise operates with lower operation frequency and fan tap than normal operation only for the set time period.
<How to enable, set start time and end time of night time low-noise>
This function is available only for the header remote controller.
1 Press the [ ] / [ ] button to select “Silent mode” on the
MENU screen, then press the [ ] button.
2 Press the [ ] button to select “ON” on the Silent mode screen,
then press the [ ] button.
3 Start the heating, cooling or hot water operation. The mark appears on the top screen during
the set-up time zone.
1 Press the [ ] / [ ] button to select “Silent mode” on the
MENU screen.
2 Press the [ ] button for 4 seconds or longer to enter the setting mode. The DN code setting
screen appears.
DN_0A: Start time (Range: 0~23, Default: 22)
0B: End time (Range: 0~23, Default: 06)
3 Press the [ ] / [ ] button to select DN or Data, then press the [ ] / [ ] button to set the
value.
The same value cannot be set to 0A and 0B.
4 Press the [ ] button. The set time is registered.
Auto mode
MENU(1/2)
Schedule timer
Night setback
Silent mode
Hot water boost
SET
ON
Silent mode
OFF
FIX
Auto mode
MENU(1/2)
Schedule timer
Night setback
Silent mode
Hot water boost
SET
Silent mode
(DN) Data
FIX