1. DESIGN METHODS
1-1. System Overview
1-1-1. Outdoor Units
Corresponding HP
Model name
Heat pump (50Hz)
Heat pump (60Hz)
Cooling capacity (kW) 1
Heating capacity (kW) 1
No.of connectable indoor units
Inverter unit
4HP 5HP 6HP
MCY-MAP0401HT MCY-MAP0501HT MCY-MAP0601HT
MCY-MAP0401HT2D MCY-MAP0501HT2D MCY-MAP0601HT2D
12.1 14.0 15.5
12.5 16.0 18.0
689
1 Rated conditions
Cooling:Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating:Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
Allocation standard of model name
No mark : Power supply specification, 1Ø/220/230/240V (50Hz)
2D : Power supply specification, 1Ø/220V, 60Hz
T : Inverter unit
H : Heat pump
Development number
Capacity rank HP × 10
R410A
M : Individual unit
Multi Compact type
MCY- M AP H T 2D