– 176 –
Using TCC-LINK central control remote controller (TCB-SC642TLE2)
Display of Unit No.
Alternate blinking
UNIT No.
No.R.C.
TEST
Display of check code
Display of Unit No.
Alternate blinking
UNIT No.
No.R.C.
TEST
Display of check code
(1) Checking and testing
When a fault occurs to an air conditioner, a
check code and indoor unit No. are displayed
on the display window of the remote
controller.
Check codes are only displayed while the air
conditioner is in operation.
If the display has already disappeared,
access error history by following the
procedure described below.
(2) Error history
The error history access procedure is described below (up to four errors stored in memory).
Error history can be accessed regardless of whether the air conditioner is in operation or shut down.
1 Push the
TEST
+
SET
buttons simultaneously and hold for at least 4 seconds.
2 The letters SERVICE CHECK” light up, and the check code “01” is displayed.
3 When a group No. is selected (blinking), if there is an error history, the UNIT No. and the
latest error history information are displayed alternately.
* During this procedure, the temperature setting feature is unavailable.
4 To check other error history items, push the
TEMP
button to select another check code
(01-04.).
5 To check check code relating to another group, push (ZONE) and (GROUP) buttons to
select a group No.
Do not push the
CL
button as it would erase the whole error history of the selected group.
6 To finish off the service check, push the
TEST
button.