9. BACKUP OPERATION (EMERGENCY OPERATION)
This product offers backup modes of operation to tide over certain emergency situations. If a fault occurs in
one of the compressors, it is possible to operate the system on an emergency basis by operating only the
remaining compressor(s), (compressor backup operation).
If one of the outdoor units fails in a combined outdoor unit system, the system can be operated on an
emergency basis by keeping only the remaining outdoor unit(s), (outdoor unit backup operation).
Perform backup operation setting in accordance with the procedure described below.
9-1. Note for Backup Operation
The method of backup operation differs according to the contents of fault as shown in the table below.
Contents of fault Method of backup operation Setting procedure
Go to 10-2.Compressor backup (see Note 1)One of the compressors in the same unit fails (see Note 1)
Go to 10-3Outdoor unit backup or cooling-
season outdoor unit backup (see
Notes 2, 3 and 4)
All the compressors in the same unit fail
A fault occurs in a compressor motor coil (e.g. a layer short-circuit)
A fault occurs in a refrigerating cycle part, fan or related part, or electrical part
A fault occurs in a temperature sensor or pressure sensor
Faulty
Faulty
Example
Prohibited
Example
Prohibited
Backed-up compressor Backed-up compressor Two backed-up compressors
Faulty
Faulty
Example
Prohibited
Backed-up outdoor unit Backed-up outdoor unit
Faulty
Faulty
Faulty
Example
Prohibited
Backed-up compressor Backed-up outdoor unit
Faulty
Backed-up outdoor unit
MMY-MAP1404
(MMY-MAP1204)
MMY-MAP1004
(MMY-MAP0804)
Example
Prohibited
Faulty
Backed-up outdoor unit
Note 1: Keep the number of backed-up outdoor units under compressor backup operation to one in the system
(single refrigerant line). For a three-compressor model, the backing up of two faulty compressors is
prohibited.
Note 2: Keep the number of backed-up outdoor units under outdoor unit backup operation to one in the system
(single refrigerant line).
Note 3: It is prohibited to combine compressor backup operation and outdoor unit backup operation.
Note 4: With a two-outdoor unit system containing an
MMYMAP1404
(or MAP1204
) and an MMY-
MAP1004
(or MMY-MAP0804
), do not preform outdoor
unit backup operation to back up the MMY-MAP1404
(or
MAP1204
).
It could lead to compressor failure due to the abnormal
operation.