Loading...
2.Putwaterinthedrainpanandmakesurethatthewaterisdrainedoutof
doors.
3.Whenconnectingextensiondrainhose,insulatetheconnectingpartof
extensiondrainhosewithshieldpipe.
Shield pipe
Drain hose
Inside the room
Extension drain hose
CAUTION
Arrangethedrainpipeforproperdrainagefromtheunit.
Improperdrainagecanresultindew-dropping.
Wall
Drain
guide
Space for pipes
Thisairconditionerhasthestructuredesigned
todrainwatercollectedfromdew,whichforms
onthebackoftheindoorunit,tothedrainpan.
Therefore,donotstorethepowercordandother
partsataheightabovethedrainguide.
OUTDOOR UNIT
Installation Place
•Aplacewhichprovidesthespacesaroundtheoutdoorunitasshowninthe
diagram
•Aplacewhichcanbeartheweightoftheoutdoorunitanddoesnotallow
anincreaseinnoiselevelandvibration
•Aplacewheretheoperationnoiseanddischargedairdonotdisturbyour
neighbors
•Aplacewhichisnotexposedtoastrongwind
•Aplacefreeofaleakageofcombustiblegases
•Aplacewhichdoesnotblockapassage
•Whentheoutdoorunitistobeinstalledinanelevatedposition,besureto
secureitsfeet.
•Theallowablelengthoftheconnectingpipe.
Model
RAS-05, 07, 10, 13J2AVG-TR
RAS-05, 07, 10, 13J2AVG-EE
RAS-05, 07, 10, 13TAVG-EE
RAS-16, 18J2AVG-TR
RAS-16, 18J2AVG-EE
RAS-16, 18TAVG-EE
Chargeless Upto15m Upto15m
Maximumlength 15m 20m
Additionalrefrigerentcharging 16–20m(20g/1m)
•Theallowableheightofoutdoorunitinstallationsite.
Model
RAS-05, 07, 10, 13J2AVG-TR
RAS-05, 07, 10, 13J2AVG-EE
RAS-05, 07, 10, 13TAVG-EE
RAS-16, 18J2AVG-TR
RAS-16, 18J2AVG-EE
RAS-16, 18TAVG-EE
Maximumheight 12m 12m
•Aplacewherethedrainwaterdoesnotraiseanyproblems
CAUTION
Whentheoutdoorunitisinstalledinaplacewherethedrainwatermight
causeanyproblems,Sealthewaterleakagepointtightlyusingasilicone
adhesiveorcaulkingcompound.
Precautions about Installation in Regions
with Snowfall and Cold Temperatures
•Donotusethesupplieddrainnipplefordrainingwater.Drainthewater
fromallthedrainholesdirectly.
•Toprotecttheoutdoorunitfromsnowaccumulation,installaholdingframe,
andattachasnowprotectionhoodandplate.
*Donotuseadouble-stackeddesign.
Front
Anchor
bolts
Snow protection plate
Snow protection hood
Snow accumulation line
Holding frame
Install at least 50 cm
above the snow
accumulation line.
At least 50 cm
Precautions for adding refrigerant
•Useascalehavingaprecisionwithatleast10gperindexlinewhen
addingtherefrigerant.
Donotuseabathroomscaleorsimilarinstrument.
•Useliquidrefrigerantwhenrefillingtherefrigerant.
Sincetherefrigerantisinliquidform,itcanfillquickly.
Therefore,performthefillingoperationcarefullyandinserttherefrigerant
gradually.
CAUTION
1.Installtheoutdoorunitwithoutanythingblockingtheairdischarging.
2.Whentheoutdoorunitisinstalledinaplacealwaysexposedtostrong
windlikeacoastoronahighstoreyofabuilding,securethenormal
fanoperationusingaductorawindshield.
3.Inparticularlywindyareas,installtheunitsuchastoavoidadmission
ofwind.
4.Installationinthefollowingplacesmayresultintrouble.
Donotinstalltheunitinsuchplaces.
•Aplacefullofmachineoil
Strong
wind
•Asaline-placesuchasthecoast
•Aplacefullofsulfidegas
•Aplacewherehigh-frequency
wavesarelikelytobegenerated
asfromaudioequipment,
welders,andmedicalequipment
8
1122950109_S04_182x257_52p_S_p70_181217_EN+TR+RU.indd 10 12/25/2018 10:46:55 AM