ELECTRICAL WORKS
Thepowersupplycanbeselectedtoconnecttoindoorunitoroutdoorunit.Chooseproperwayandconnectthepowersupplyandconnectingcablebyfollow
theinstructionasfollowing.
Model 05k 07k 10k 13k 16k 18k
Powersource 50Hz,220–240VSinglephase
Maximumrunningcurrent 5.0A 5.4A 7.2A 7.4A 9.0A 9.25A
Circuitbreakerrating 6.5A 7.0A 9.0A 9.5A 11.5A 12.0A
Powersupplycable H07RN-For60245IEC66(1.5mm
2
ormore)
H07RN-For60245IEC66
(2.5mm
2
ormore)
Connectingcable H07RN-For60245IEC66(1.5mm
2
ormore)
Wiring Connection
Indoor unit
Wiring of the connecting cable can be carried out without removing the
front panel.
1.Removetheairinletgrille.
Opentheairinletgrilleupwardandpullittowardyou.
2.Removetheterminalcoverandcordclamp.
3.Inserttheconnectingcable(accordingtothelocalcords)intothepipe
holeonthewall.
4.Takeouttheconnectingcablethroughthecableslotontherearpanelso
thatitprotrudesabout20cmfromthefront.
5.Inserttheconnectingcablefullyintotheterminalblockandsecureit
tightlywithscrews.
6.Tighteningtorque:1.2N·m(0.12kgf·m)
7.Securetheconnectingcablewiththecordclamp.
8.Fixtheterminalcover,rearplatebushingandairinletgrilleontheindoor
unit.
Air inlet grille
Front panel
Screw
Screws
Terminal cover
Cord clamp
How to install the air inlet grille on the indoor
unit
•Whenattachingtheairinletgrille,thecontraryoftheremovedoperationis
performed.
Outdoor unit
1.Removethevalvecover,theelectricpartscoverandthecordclampfrom
theoutdoorunit.
2.Connecttheconnectingcabletotheterminalasidentifiedbythe
matchingnumbersontheterminalblockofindoorandoutdoorunit.
3.Insertthepowercordandtheconnectingcablecarefullyintotheterminal
blockandsecureittightlywithscrews.
4.Usevinyltape,etc.toinsulatethecordswhicharenotgoingtobeused.
Locatethemsothattheydonottouchanyelectricalormetalparts.
5.Securethepowercordandtheconnectingcablewiththecordclamp.
6.Attachtheelectricpartscoverandthevalvecoverontheoutdoorunit.
Terminals block
Valve cover
11
1122950109_S04_182x257_52p_S_p70_181217_EN+TR+RU.indd 13 12/25/2018 10:46:57 AM