7-2. Operation Data
<Cooling>
<Heating>
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
2. Connecting piping condition : 5 m
Temperature
condition (°C)
Indoor Outdoor
27/19 35/
Model name
RAS-
B10SKVP-E
10SKVP-ND
B13SKVP-E
13SKVP-ND
B16SKVP-E
16SKVP-ND
Standard
pressure
P (MPa)
1.0 to 1.2
0.9 to 1.1
0.8 to 1.0
Heat exchanger
pipe temp.
T1 (°C) T2 (°C)
13 to 15 36 to 39
10 to 13 37 to 39
8 to 11 37 to 40
Indoor
fan mode
High
High
High
Outdoor
fan mode
High
High
High
Compressor
revolution
(rps)
35
56
82
Temperature
condition (°C)
Indoor Outdoor
20/ 7/6
Model name
RAS-
B10SKVP-E
10SKVP-ND
B13SKVP-E
13SKVP-ND
B16SKVP-E
16SKVP-ND
Standard
pressure
P (MPa)
2.1 to 2.3
2.4 to 2.6
2.8 to 3.0
Heat exchanger
pipe temp.
T1 (°C) T2 (°C)
37 to 39 3 to 5
41 to 44 2 to 4
48 to 50 2 to 4
Indoor
fan mode
High
High
High
Outdoor
fan mode
High
High
High
Compressor
revolution
(rps)
46
62
85