Outdoor Unit : RAS-3M26YAV-E
<Heating>
NOTES :
Model of Indoor unit 10 : RAS-M10UKV-E3, 13 : RAS-M13UKV-E3, 16 : RAS-M16UKV-E3
NOTES :
(1) Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bend.
(Thermistor thermometer)
(2) Connecting piping condition : 5 meters x 3 units (5m/each indoor unit)
Temperature
condition
Operating combination
(Unit)
Heat exchanger
pipe temp.
Indoor Outdoor
No. of
o
p
eratin
g
units
ABC
Standard
p
ressure
P (MPa)
T1 (°C) T2 (°C)
Indoor
fan
Outdoor
fan
Com
ressor
revolution
(rps)
10 ––2.6 to 2.8 44 to 46 2 to 4 High MED 40
13 ––3.3 to 3.5 52 to 54 1 to 3 High MED 50
1 unit
16 ––3.5 to 3.7 55 to 57 1 to 3 High MED 53
10 10 2.7 to 2.9 45 to 47 0 to 2 High MED 62
13 10 2.8 to 3.0 45 to 47 0 to 2 High MED 63
16 10 2.9 to 3.1 46 to 48 0 to 2 High MED 65
13 13 2.9 to 3.1 46 to 48 0 to 2 High MED 66
16 13 3.1 to 3.3 47 to 49 0 to 2 High MED 68
2 units
16 16 3.3 to 3.5 50 to 52 0 to 2 High MED 70
10 10 10 2.3 to 2.5 38 to 40 1 to 1 High MED 72
13 10 10 2.3 to 2.5 38 to 40 1 to 1 High MED 72
16 10 10 2.3 to 2.5 38 to 40 1 to 1 High MED 72
13 13 10 2.3 to 2.5 38 to 40 1 to 1 High MED 73
16 13 10 2.3 to 2.5 38 to 40 1 to 1 High MED 73
13 13 13 2.3 to 2.5 38 to 40 1 to 1 High MED 73
16 16 10 2.3 to 2.5 38 to 40 1 to 1 High MED 73
16 13 13 2.5 to 2.7 37 to 39 2 to 0 High MED 74
27 / 7 / 6
3 units
16 16 13 2.5 to 2.7 37 to 39 2 to 0 High MED 74