9-3. Outdoor Unit
9-3-1. Accessory and
Installation Parts
Outdoor unit installation manual x 1
Specifications x 1
Owner's manual x 1
S
PEC
IF
IC
ATIO
NS
1
2
3
9-3-2. Refrigerant Piping
Piping kit used for the conventional refrigerant
cannot be used.
Use copper pipe with 0.8 mm or more thick-
ness.
Flare nut and flare works are also different from
those of the conventional refrigerant. Take out the
flare nut attached to the main unit of the air condi-
tioner, and use it.
9-3-3. Installation Place
A place which provides the spaces around the
outdoor unit.
A place where the operation noise and discharged
air do not disturb your neighbors.
A place which is not exposed to a strong wind.
A place which does not block a passage.
When the outdoor unit is to be installed in an
elevated position, be sure to secure its feet.
There must be sufficient spaces for carrying the
unit into and out of the site.
A place where the drain water does not raise any
problem.
9-3-4. Optional Installation Parts
(Local Supply)
CAUTION
1. Install the outdoor unit without anything
blocking the air discharging.
2. When the outdoor unit is installed in a place
exposed always to a strong wind like a coast
or on a high story of a building, secure the
normal fan operation using a duct or a wind
shield.
3. Specially in windy area, install the unit to
prevent the admission of wind.
A
B
C
Parts name
Refrigerant piping
Liquid side : Ø6.35 mm
Gas side : Ø9.52 mm or Ø12.7 mm
Pipe insulating material
(polyethylene foam, 6 mm thick)
Putty, PVC tapes
Q’ty
Each one
1
Each one
9-3-5. Optional Installation Parts
(Separate Sold)
Parts name
RB-M43RE Reducer (Ø12.7 Ø9.52)
RB-M34EE Expander (Ø9.52 Ø12.7)
Strong
wind
Fig. 9-3-1
4. Installation in the following places may result
in trouble. Do not install the unit in such
places.
A place full of machine oil.
A place full of sulfide gas.
A place where high-frequency waves are
likely to be generated as from audio
equipment, welders, and medical equip-
ment.

Table of Contents