– 27 –
Item Operation flow and applicable data, etc. Description
2. Indoor fan
motor
control
5) Self-clean operation
When performing self-clean operation after stopping the cooling
operation, the mode becomes LL (M07, M10, M13), L (M16).
[Self-clean ] is displayed.
Cool air discharge preventive control
1) In heating operation, the indoor fan is controlled based on the
detected temperature of Tc sensor or Tcj sensor. As shown below,
the upper limit of the revolution frequency is restricted.
However B zone is assumed as C zone for 6 minutes and after when
the compressor activated. In defrost operation, the control value of
Tc is shifted by 6°C.
In D and E zones, the
priority is given to air volume
selection setup of remote
controller.
In A zone while thermo is
ON, [PRE-HEAT (Heating
ready)] is displayed.
(˚C)
32
30
28
26
20
16
Tc
Tcj
HH
H
L
UL
OFF
E zone
D zone
C zone
B zone
A zone