– 89 –
Using the Service monitor with the [ MONITOR] button during the test mode
2. Function selection setup
Perform the advanced settings for the air conditioner.
Carry out the setting operation while the indoor unit is stopped. (Turn off the air conditioning unit before starting
the setting operation.)
Push the [ MONITOR] button
1 Push the [ MENU] button to display the menu screen.
2 Push and hold the [ MENU] button and the [ ] button at the
same time to display the “Field setting menu”.
Æ Push and hold the buttons for more than 4 seconds.
3 Push the [ ] / [ ] button to select “5. FC setting” on the
“Field setting menu” screen, then push the “ Set” [
F2] button.
Æ The fan of the indoor unit operate.
Æ Move the cursor to select “Function code” with the “ <” [
F1] button, then set “Function code” with the [ ] / [ ]
button.
Æ Move the cursor to select “data” with the “ >” [ F2]
button, then set “data” with the [ ] / [ ] button.
4 Push the [ MENU] button to set the other Function codes. After
“Continue?” is displayed on the screen, push the “
Yes” [ F1] button.
5 Push the “ No” [ F2] button to finish the setting
operation. “ ” appears on the screen for a while, then the screen
returns to the “Field setting menu” screen.
Æ Pushing the “ No” [ F2] button displays the unit
selection screen when the group control is used. Push the [
CANCEL] button on the unit selection screen to finish the setting
operation. “ ” appears on the screen for a while, then the screen
returns to the “Field setting menu” screen.
Tes t
Room A
12:00
Mode
Fan Speed
Cool
Monitor Function
Code
00
Data
0024
Return
Refer to “3. Monitor function” for details.
1.Test mode
2.Register service info.
3.Alarm history
4.Monitor function
5.FC setting
Field setting menu
Return
Set
FC setting
Code
(FC) Data
Return
10 0000
Fix
<>
FC setting
Code
(FC) Data
Return
10 0001
Fix
<>
Return
Continue?
NoYes
FC setting
Set
<
>
Yes
No
No