– 90 –
Function selection item No. (FC) list
3. Monitor function
The sensor temperature or operational status of indoor unit, outdoor unit, or remote controller can be monitored.
FC Item Contents At shipment from factory
01 Filter sign lighting time
0000: None
0002: 2500H
0004: 10000H
0001: 150H
0003: 5000H
0005: Clogging sensor used
0000: None
02 Filter stain level
0000: Standard
0001: Heavy stain (Half of standard time)
0000: Standard
06 Heating suction temp. shift
0000: No shift
0002: +2°C
to
0001: +1°C
0010: +10°C
0002: +2°C
10 Type 0000: IMS duct 0000: IMS duct
11 Indoor unit capacity 0000: Undecided 0001 to 0034
According to capacity type
M07: 0001
M10: 0003
M13: 0005
M16: 0007
17 Cooling suction temp. shift
0000: No shift
0002: +2°C
to
0001: +1°C
0010: +10°C
0000: No shift
1E
In automatic cooling/heating,
temp. width of cool heat,
heat cool mode selection
control point
0000: 0 deg to 0010: 10 deg
0003: 3 deg
(Ts±1.5)
(Cool/heat are reversed with ± (Data value) /
2 against the set temperature)
28
Automatic reset of power
failure
0000: None 0001: Provided 0000: None
32 Sensor selection
0000: Body TA
sensor
0001: Remote controller
sensor
0000: Body sensor
5d External static pressure
0000: Depends on
DIPSW 501-1,-2
1 Push the [ ] / [ ] button to select “4. Monitor
function” on the “Field setting menu” screen, then push
the “ Set” [ F2] button.
Æ Push the [ ] / [ ] button to select the code to check
data.
2 Push the [ CANCEL] button to return to the “Field
setting menu” screen.
SET DATA External static pressure
0000
Depends on
DIPSW 501-1,-2
0001 10 Pa
0002 20 Pa
0003 35 Pa
0004 45 Pa
Monitor function
Code
00
Data
0024
Return
Set
Item code Data name Unit
01 Room temperature
(Remote controller)
°C
02 Indoor suction temperature (TA) °C
03 Indoor heat exchanger (Coil)
temperature (TCJ)
°C
04 Indoor heat exchanger (Coil)
temperature (TC)
°C
07 Indoor fan revolution frequency rpm
F2 Indoor fan calculated operation
time
×100h
F3 Filter sign time ×1h
F8 Indoor discharge temperature*1 °C
Indoor unit data
Item code Data name Unit
60 Outdoor heat exchanger (Coil)
temperature (TE)
°C
61 Outside temperature (TO) °C
62 Compressor discharge
temperature (TD)
°C
63 Compressor suction temperature
(TS)
°C
6A Operation current (× 1/10) A
70 Compressor operation frequency rps
72 Outdoor fan revolution frequency
(Lower)
rpm
F1 Compressor calculated operation
time
×100h
Outdoor unit data

Table of Contents