– 42 –
Item
3. Outdoor fan
motor control
(Continued)
Operation flow and applicable data, etc.
Heating operation
1) Operation is performed at the MAX revolutions shown in the left tables for 3 minutes after com-
pressor operation starts and for 1 minute after defrosting operation ends.
2) Following 1) above, operation is performed at the outdoor unit fan revolutions shown in the left
tables according to the outdoor heatexchanger sensor (TE sensor) temperature.
RAS-M18GAV-E
To: Outdoor sensor temp. (°C)
RAS-M14GAV-E
To: Outdoor sensor temp. (°C)
Description
Compressor revolution (rps)
Fan revolution
To > 10°C
Normal operation 5.5 < To ≤ 10
–5 < To ≤ 5.5
To ≤ –5
To > 10°C
Econo operation
5.5 < To ≤ 10
–5 < To ≤ 5.5
To ≤ –5
To is abnormal —
~20 ~48 48~
MIN MAX MIN MAX MIN MAX
250 400 250 600 250 700
250 400 250 700 250 750
250 600 250 750 250 800
250 600 250 750 250 800
250 400 250 500 250 600
250 400 250 600 250 700
250 600 250 700 250 700
250 600 250 700 250 700
250 400 250 700 250 750
Compressor revolution (rps)
Fan revolution
To > 10°C
Normal operation 5.5 < To ≤ 10
–5 < To ≤ 5.5
To ≤ –5
To > 10°C
Econo operation
5.5 < To ≤ 10
–5 < To ≤ 5.5
To ≤ –5
To is abnormal —
~20 ~60 60~
MIN MAX MIN MAX MIN MAX
250 400 250 600 250 700
250 400 250 700 250 750
250 600 250 750 250 800
250 600 250 750 250 800
250 400 250 500 250 600
250 400 250 600 250 700
250 600 250 700 250 700
250 600 250 700 250 700
250 400 250 700 250 750
TE
24°C
21°C
18°C
15°C
Zone A:
Zone B:
Zone C:
Zone D:
Zone E:
Zone A: The fan revolutions are decreased by 100 rpm every 20 seconds
(to the MIN revolutions).
When Zone A operation continues for 5 minutes, the compressor
is stopped and then restarted.
Zone B: The fan revolutions are decreased by 100 rpm every 20 seconds
(to the MIN revolutions).
Zone C: The fan revolutions are decreased by 50 rpm every 20 seconds
(to the MIN revolutions).
Zone D: The fan revolutions are maintained at the current revolutions.
Zone E: The fan revolutions are increased by 50 rpm every 20 seconds
(to the MAX revolutions).