– 24 –
6-2. Operation Data
<Cooling>
Temperature
No. of
condition (°C)
operating
Indoor Outdoor
units
1 unit
20/– 7/6
2 units
Operating combination
Standard
(Unit)
pressure
AB
P (MPa)
M13YKV-E 3,5 to 3,7
M10YKV-E 3,3 to 3,5
M13YKV-E M10YKV-E 2,5 to 2,7
M10YKV-E M10YKV-E 2,5 to 2,7
Heat exchanger
Indoor Outdoor Compressor
pipe temp.
fan fan revolution
T1 (°C) T2 (°C)
mode mode (rps)
53 to 55 0 to 2 High High 79
48 to 50 0 to 2 High MED. 63
41 to 43 –2 to 0 High High 97
41 to 43 –2 to 0 High High 97
Temperature
No. of
condition (°C)
operating
Indoor Outdoor
units
1 unit
27/19 35/–
2 units
Operating combination
Standard
(Unit)
pressure
AB
P (MPa)
M13YKCV-E
0,7 to 0,9
M13YKV-E
M10YKCV-E
0,9 to 1,1
M10YKV-E
M13YKCV-E M10YKCV-E
0,8 to 1,0
M13YKV-E M10YKV-E
M10YKCV-E M10YKCV-E
0,8 to 1,0
M10YKV-E M10YKV-E
Heat exchanger
Indoor Outdoor Compressor
pipe temp.
fan fan revolution
T1 (°C) T2 (°C)
mode mode (rps)
9 to 11 46 to 48 High High 62
11 to 13 45 to 47 High MED. 38
11 to 13 50 to 52 High High 74
10 to 12 50 to 52 High High 74
<Heating>
NOTES :
(1) Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
(2) Connecting piping condition : 5 m x 2 units