– 4 –
RAS-M10YKCV-E, RAS-M13YKCV-E / RAS-M18YACV-E
For performance when each indoor unit is combined with other unit, refer to the separate table.
The specifications may be subject to change without notice for purpose of improvement.
Unit model Indoor
Outdoor
Cooling capacity (kW)
Cooling capacity range (kW)
Power supply
Electric Indoor Unit model
characteristics
Running current (A)
Power consumption (W)
Power factor (%)
Outdoor Unit model
Running current (A)
Power consumption (W)
Power factor (%)
Starting current (A)
COP
Operating noise Indoor Unit model
High (dB•A)
Medium (dB•A)
Low (dB•A)
Outdoor Unit model
10-1 indoor unit operating (dB•A)
13-1 indoor unit operating (dB•A)
2 indoor unit operating (dB•A)
Indoor unit Unit model
Dimension Height (mm)
Width (mm)
Depth (mm)
Net weight (kg)
Fan motor output (W)
Air flow rate (m
3
/h)
Outdoor unit Unit model
Dimension Height (mm)
Width (mm)
Depth (mm)
Net weight (kg)
Compressor Motor output (W)
Type
Model
Fan motor output (W)
Air flow rate (m
3
/h)
Piping connection Type
Indoor unit Unit model
Liquid side
Gas side
Outdoor unit Unit model
A unit liquid side/gas side
B unit liquid side/gas side
Maximum length (per unit) (m)
Maximum length (total) (m)
Maximum chargeless length (m)
Maximum height difference (m)
Refrigerant Name of refrigerant
Weight (kg)
Wiring connection Power supply
Interconnection
Usable temperature range Indoor (°C)
Outdoor (°C)
Accessory Indoor unit Installation plate
Wireless remote control
Label
Remote control holder
Pan head wood screw
Purifying filter
Deodorizing filter
Batteries
Mounting screw
Installation manual
Outdoor unit Installation manual
Owner's manual
RAS-M10YKCV-E, RAS-M13YKCV-E
RAS-M18YACV-E
5,2
1,4 – 6,2
220 – 230 – 240V – 1Ph – 50 Hz
RAS-M10YKCV-E RAS-M13YKCV-E
0,15 0,15
30 30
87 87
RAS-M18YACV-E
7,90 / 7,57 / 7,28
1660
95%
8,20 / 7,87 / 7,58
3,02
RAS-M10YKCV-E RAS-M13YKCV-E
36 39
33 35
30 30
RAS-M18YACV-E
42
46
46
RAS-M10YKCV-E RAS-M13YKCV-E
265 265
790 790
189 189
88
19 19
470 520
RAS-M18YACV-E
550
780
270
42
1100
Twin rotary type with DC-inverter variable speed control
DA130A1F-21F
40
2060
Flare connection
RAS-M10YKCV-E RAS-M13YKCV-E
Ø6,35 Ø6,35
Ø9,52 Ø9,52
RAS-M18YACV-E
Ø6,35 / Ø9,52
Ø6,35 / Ø9,52
20
30
30
10
R410A
1,15
3 Wires : includes earth
4 Wires : includes earth
21 – 32
21 – 43
1
1
2
1
2 (Ø3,1 x 16L)
1
1
2
6 (Ø4 x 25L)
1
1
1