– 31 –
Compressor revolution (rps) ~ 17,4 ~ 47,9 48 ~
Outdoor temp. sensor
TO 38°C 500 (rpm) 820 (rpm) 820 (rpm)
TO
TO < 38°C 500 (rpm) 700 (rpm) 820 (rpm)
ECONO. operation
TO 38°C 500 (rpm) 700 (rpm) 820 (rpm)
TO < 38°C 500 (rpm) 500 (rpm) 700 (rpm)
TO is abnormal 700 (rpm) 700 (rpm) 820 (rpm)
8-1-8. Outdoor Fan Control (DC Fan Motor)
Although the outdoor fan motor drives the outdoor fan by non-step variable system of the revolution speed, the
revolution speed is restricted to three steps on the convenience of controlling. If a strong wind is lashing outside
of the room, the operation may be continued as the outdoor fan stops in order to protect the outdoor fan motor.
If a fan lock occurred due to entering of foreign matter, the air conditioner stops and an alarm is displayed.
<COOL, DRY>
Table 8-1-3
8-2. Description of Operation Circuit
Turning [ON] the breaker flashes the operation
lamp.
This is the display of power-ON (or notification of
power failure).
When pushing [START/STOP] button of the
remote control, receive sound is issued from the
main unit, and the next operations are performed
together with opening the vertical air flow louvers.
8-2-1. Fan Only Operation
(The Remote Control MODE Button is
Set to the FAN ONLY Operation)
Once the setting is made, the operation mode is
memorized in the microcomputer so that the
same operation can be effected thereafter simply
by pushing [START/STOP] button.
When the FAN button is set to the AUTO position,
the indoor fan motor operates as shown in Fig. 8-
2-1. When the FAN SPEED button is set to
LOW, MED, or HIGH, the motor operates with a
constant air flow.
ECONO. mode cannot be set.
0
Set
temp.
+0,5
+1
+1,5
+2
+2,5
+3
(Set temp.) 25˚C
˚C
M+
*1
*1
*1
L–
(Room temp.) – (Set temp.)
NOTE :
*1: Calculated from difference in motor speed of M+
and L–, and controlled.
Fig. 8-2-1 Auto setting of air flow
<HEAT>
Table 8-1-4
Compressor revolution (rps) ~ 28,1 ~ 72,9 73,0 ~
Outdoor temp. sensor
TO 5°C 450 (rpm) 650 (rpm) 820 (rpm)
TO
TO < 5°C 650 (rpm) 650 (rpm) 820 (rpm)
ECONO. operation
TO 5°C 450 (rpm) 450 (rpm) 650 (rpm)
TO < 5°C 450 (rpm) 650 (rpm) 650 (rpm)
TO is abnormal 450 (rpm) 650 (rpm) 820 (rpm)