– 31 –
Compressor revolution (rps) ~ 17,4 ~ 47,9 48 ~
Outdoor temp. sensor
TO ≥ 38°C 500 (rpm) 820 (rpm) 820 (rpm)
TO
TO < 38°C 500 (rpm) 700 (rpm) 820 (rpm)
ECONO. operation
TO ≥ 38°C 500 (rpm) 700 (rpm) 820 (rpm)
TO < 38°C 500 (rpm) 500 (rpm) 700 (rpm)
TO is abnormal 700 (rpm) 700 (rpm) 820 (rpm)
8-1-8. Outdoor Fan Control (DC Fan Motor)
Although the outdoor fan motor drives the outdoor fan by non-step variable system of the revolution speed, the
revolution speed is restricted to three steps on the convenience of controlling. If a strong wind is lashing outside
of the room, the operation may be continued as the outdoor fan stops in order to protect the outdoor fan motor.
If a fan lock occurred due to entering of foreign matter, the air conditioner stops and an alarm is displayed.
<COOL, DRY>
Table 8-1-3
8-2. Description of Operation Circuit
• Turning [ON] the breaker flashes the operation
lamp.
This is the display of power-ON (or notification of
power failure).
• When pushing [START/STOP] button of the
remote control, receive sound is issued from the
main unit, and the next operations are performed
together with opening the vertical air flow louvers.
8-2-1. Fan Only Operation
(The Remote Control MODE Button is
Set to the FAN ONLY Operation)
• Once the setting is made, the operation mode is
memorized in the microcomputer so that the
same operation can be effected thereafter simply
by pushing [START/STOP] button.
• When the FAN button is set to the AUTO position,
the indoor fan motor operates as shown in Fig. 8-
2-1. When the FAN SPEED button is set to
LOW, MED, or HIGH, the motor operates with a
constant air flow.
• ECONO. mode cannot be set.
0
Set
temp.
+0,5
+1
+1,5
+2
+2,5
+3
(Set temp.) 25˚C
˚C
M+
*1
*1
*1
L–
(Room temp.) – (Set temp.)
NOTE :
*1: Calculated from difference in motor speed of M+
and L–, and controlled.
Fig. 8-2-1 Auto setting of air flow
<HEAT>
Table 8-1-4
Compressor revolution (rps) ~ 28,1 ~ 72,9 73,0 ~
Outdoor temp. sensor
TO ≥ 5°C 450 (rpm) 650 (rpm) 820 (rpm)
TO
TO < 5°C 650 (rpm) 650 (rpm) 820 (rpm)
ECONO. operation
TO ≥ 5°C 450 (rpm) 450 (rpm) 650 (rpm)
TO < 5°C 450 (rpm) 650 (rpm) 650 (rpm)
TO is abnormal 450 (rpm) 650 (rpm) 820 (rpm)