– 70 –
(Example of 4-lines wiring)
(Real line: Wiring, Broken line: Refrigerant pipe)
For the above example, perform setting by
connecting singly the wired remote controller
without remote controller inter-unit wire.
Group address
Individual : 0000
Header unit : 0001
Follower unit : 0002
In case of group control
Outdoor
Indoor
A B
A B
1 2 3
Indoor
A B
1 2 3
Indoor
A B
1 2 3
1 2 3
Outdoor
1 2 3
Remote controller
Line address → 1
Indoor unit address → 1
Group address → 1
2
2
2
3
3
2
4
4
2
Indoor
A B
1 2 3
Outdoor
1 2 3
Outdoor
1 2 3
In case that addresses of the indoor units will be
determined prior to piping work after wiring work
• Set an indoor unit per a remote controller.
• Turn on power supply.
1
2
3
4
5
6
7
8
9
10
11
12
9-3. Address Setup (Manual Setting from Remote Controller)
Push [MENU] and [▼] buttons
simultaneously for at least 10 seconds.
Push [▼] or [▲] button to adjust the
indoor unit number, and push
[TIME] button to confirm.
Line address settings:
Using [▼] or [▲] button,
set the CODE No. to [12].
Use [MENU] button to adjust the flash from
CODE No. to SET DATA on the left.
Use [▼] or [▲] button to set the line address.
Push [MENU] button to adjust the flash to
CODE No. on the right after pushing [TIME] button
to confirm.
Setting of indoor unit address:
Using [▼] or [▲] button, set the CODE No. to [13].
Use [MENU] button to adjust the flash from CODE No. to SET DATA on the left. Use [▼] or
[▲] button to set the address of the indoor unit.
Push [MENU] button to adjust the flash to CODE No. on the right after pushing [TIME]
button to confirm.
Setting of group address:
Using [▼] or [▲] button, set the CODE No. to [14].
Use [MENU] button to adjust the flash from CODE No. to SET DATA on the left. Set 0000
as a standalone unit, set 0001 as a main unit, set 0002 as a sub unit.
Push [MENU] button to adjust the flash to CODE No. on the right after pushing [TIME]
button to confirm.
Push [ON/OFF] button to complete the setting when
the setting is completed.
• To change the settings of another indoor unit,
repeat from step 1.
• Repeat steps 1 to 9 until all indoor unit addresses are
set and with no duplication.
SET DATA [MENU] [TIME] [▼] [▲] [ON/OFF] CODE No.