8-1-1. Test Run Setup on Remote Controller
<Wired remote controller>
8. SETUP AT LOCAL SITE AND OTHERS
8-1. Indoor Unit
1. Push [TIME] and [] buttons and hold for more than 10 seconds. [TEST] is displayed on the display screen,
and mode selection in Test mode is allowed.
2. Push [ON/OFF] button to start the air conditioner.
3. Using [MENU] button to change the cooling or heating mode
Do not use [MENU] button to change modes other than cooling and heating modes.
Under heating and cooling operations, a command for fixing test running frequency will be output.
The temperature cannot be adjusted during the test run, but the air volume can be selected.
Fault detection is operating normally, but do not use this function in "test run" as this will cause load on the
equipment.
4. Push [ON/OFF] button to stop the operation after the test run.
5. Push [TIME] button to clear the TEST mode, [TEST] display in the display part disappears and the status
returns to the normal stop status.
(To prevent a continuous test run operation, it will be automatically shut down after 60 minutes by the remote
controller.)