EasyManua.ls Logo

Toshiba S2E21 - Set Point List; Ordering Information

Toshiba S2E21
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SET
POINT
LIST
ORDERING
INFORMATION
Item
Page
Code
Value
Factory
Set Point
Set
Point
CT
rating
P20
CT
5
-
2000
A
5A
ZCT
rating
P20
ZCT
50
-
100
A
50A
Rated
current
P20
IN
40-100%
40%
Heating
time
constant
of
stator
P21
TR
10
-
165
MIN
10
MIN
Cooling
time constant
of
stator
P21
TD
10
-
500
MIN
10
MIN
Allowable
stator
temperature
rise
P21
6SM
60
-
125
DEG
(RISE)
60
C
Rated
stator
temperature
rise
P21
9SN
10
-
125
DEG
RISE
50
C
INST
operating
current
P22
I
INST
5
-
17 x
IN
0
OFF
OC
operating
current
P22
IOC
1
.5
-
10 x
IN
0
OFF
OC
operating
time
P22
TOC
0
.3
- 1
SEC
0
.3
SEC
Unbalance
ratio
P23
UB
5-30%
0
OFF
UC
operating
current
P23 IUC
30
-
80%
x
IN
0(OFF)
UC
operating
time
P23
TUC
1 -
5
SEC
1
SEC
G
.F
.
operating
current
P24
IOCG
5
-
40%
x
ZCT
0
OFF
G
.F
.
operating
time
P24
TOCG
0
.1
- 1
.5
SEC
0
.1
SEC
Allowable
locked
rotor
time
in
COLD
condition
P25
TSC
1 -
130
SEC
0(OFF)
Starting
current
P25
IST
1
.5
-
15 x
IN
6 times
IN
Starting
time
P25
TST
1 -
60
SEC
1
SEC
Data
communication
P26
-
Slave
No
.
:
1
-31
Parity
:
None,
Even
Remote
set
:
No/Yes
1
0
(NONE)
0 (NO)
Memory
card
P27
-
Alarm,
reset
level
P28
P33
-
-
- -
Output
configuration
P29
P30
-
-
Output
selection
fail-safe/non-fail-safe
OL
Trip
non-fail-safe
Analog
output
P31
ATD
Output
selection
0
NONE
RTD
P32
RTD1-8
RTD
selection
0
NONE
Auto-learning
P34 P34
IST
:
Tst
:
Off/On
TR
:
TD
:
OFF
Description
Order
Code
Model
No
.
Function
Accessory
Items
Motor
protection
relay
S2E21
-
C1
A
Standard
Memory
card
(Qty
1)
Motor
protection
relay
S2E21
-
ClAA
With
DG
for
ungrounded
system
50Hz
Memory
card
(Qty
1)
Motor
protection
relay
S2E21
-
C1
AB
With
DG
for
ungrounded
system
60Hz
Test
plug
for
DDG
(Qty
1)
Motor
protection
relay
S2E21
-
C1
AC
With
DG
for
10A
grounded
system
60Hz
Motor
protection
relay
S2E21
-
C1
AD
With
DG
for
10A
grounded
system
50Hz
Motor
protection
relay
S2E21
-
C1
AE
With
DG
of
capacitory
voltage
division
type
50Hz
Motor
protection
relay
S2E21
-
C1 AF
With
DG
of
capacitory
voltage
division
type
60Hz
Monitor software
S2E21
-SE
3
.5
inch
2HDFDD
Quantity
1
Converter
4D9E0054GOO2
ADP-6237B
Necessary,
when
data
communication
(RS485)
used
Cable
(Qty
1)
Memory
card
Reader
./Writer
4D9E0054GOO1
MZA5001
AAA
Necessary,
when
memory
card
used
in
programming
from
computer
Cable
(Qty
1)
M
e
m
o
ry
ca
r
d
4D
9
E
005
7
GOO
1
M
C
A
5
101
BAA
S-RAM,
32-kbyte,
40
pin

Other manuals for Toshiba S2E21