166
Check code name
[F13] / [43]
(d07 / AI-NET)
Check code name
TH sensor error
Cause of operation
IGBT built-in sensor error in A3-IPDU
Sub-code: 01: Compressor 1 side 02: Compressor 2 side
This error code means IGBT built-in temperature sensor error.
Check connection of connectors CN06 on IPDU P.C. board and CN600 on I/F P.C. board.
If sensor is normal, replace IPDU P.C. board.
Check code name
[F15] / [18]
(d07 / AI-NET)
Check code name
Outdoor temp sensor miscabling
(TE1, TL)
Cause of operation
1. Misinstallation and misconnection of TE1
sensor and TL sensor
2. Resistance characteristics error of TE1
sensor and TL sensor
3. Outdoor P.C. board (I/F) error
YES
YES
YES
NO
NO
NO
Are installed positions of
TE1 sensor and TL sensor correct?
Are connection of TE1 sensor connector
and TL sensor connector normal?
Are resistance characteristics of
TL sensor and TE1 sensor normal?
Check outdoor I/F P.C. board.
Defect
Replace
Correct connection of connectors.
Correct connection of connectors.
Correct installed positions of
TE1 sensor and TL sensor.
Outdoor unit temperature sensor characteristics
See TE1 sensor : Characteristics-5
See TL sensor : Characteristics-2.
TE1 sensor : Outdoor heat exchanger temp sensor
TL sensor : Temp sensor between liquid tanks of outdoor PMV1/2
Outdoor I/F P.C. board
TE1 sensor : CN505, Green
TL sensor : CN521, White