Toshiba Super MMY-MAP0601HT8 - TK4 Temperature Detective Circuit Error

Toshiba Super MMY-MAP0601HT8
270 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
181
Check code name
[H16] / [d7]
(d07 / AI-NET)
Check code name
TK4 temperature detective circuit error
(Sub-code: 04)
Cause of operation
1. Detachment of TK4 sensor, miscabling,
characteristics error of resistance value
2. Check clogging and malfunction of
SV3E valve circuit.
3. Oil-equalization circuit error
(Check capillary clogging, strainer
clogging)
4. Refrigerant stagnation in compressor
shell
Is not TK4 sensor detached?
Is there no miscabling or misinstallation
on TK1/TK2/TK3/TK4 sensors?
Check the clogging of SV3E valve.
*1 Refer to item [H07] error.
*2 If OCR operates even after manual reset of OCR, check whether the wiring to the
current sensor (TO2) of Comp-IPDU is correct or not.
Correct miscabling/misinstallation.
TK1: CN514
TK2: CN515
TK3: CN516
TK4: CN523
( )
YES
YES
YES
NO
NO
NO
Replace SV3E valve.
Correct installation of sensor.
Are characteristics of TK4 sensor
resistance value normal?
Check the clogging of SV3E valve.
(*1)
Error
No error
Does OCR of MG-SW operate?
YES
NO
Reset OCR manually.(*2)
Sensor error Replace
Check I/F P.C. board

Table of Contents