EasyManua.ls Logo

Toshiba Super MMY-MAP0601HT8 - Outdoor Pressure Sensor Miscabling

Toshiba Super MMY-MAP0601HT8
270 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
167
Check code name
[F16] / [43]
(d07 / AI-NET)
Check code name
Outdoor pressure sensor miscabling
(Pd, Ps)
Cause of operation
1. High-pressure Pd sensor and low-
pressure sensor Ps are exchanged.
2. Output voltage of each sensor is zero.
YES
YES
YES
NO
NO
NO
Sensor error
Replace
Correct connection of connectors.
Pd sensor: CN501, Red
Ps sensor: CN500, White
Are connection of Pd sensor and
Ps sensor connectors correct?
Are output voltage characteristics of
Pd sensor and Ps sensor normal?
Are Pd/Ps output values Pd>Ps
during compressor operation?
Check outdoor I/F P.C. board.
Defect
Replace
* Value can be confirmed by 7-segment display function on outdoor I/F P.C. board.
Pd SW01/02/03=1/1/2
Ps SW01/02/03=1/2/2
* 1 Pressure (Check joint) by pressure gauge
2 Pressure display on 7-segment display
3 Output voltage of I/F P.C. board
If 1 and 2, 3 are different, an error of pressure sensor itself is considered.
If 2 and 3 are different, check interface P.C. board.
Check compressor.