Toshiba Super MMY-MAP0601HT8 - G-Tr Short-Circuit Protection Error

Toshiba Super MMY-MAP0601HT8
270 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
202
Check code name
[P26] / [14]
(d07 / AI-NET)
Check code name
G-Tr short-circuit protection error
Cause of operation
1. Outdoor unit power error
2. IPDU error/Cable connection error
3. Compressor error
4. IPDU P.C. board error
Sub-code: 01: Compressor 1 side 02: Compressor 2 side
Is power voltage of outdoor unit normal?
Is there no fusing of AC30A fuse?
Replace IPDU P.C. board.
Is compressor normal?
Is wire connector connection
on IPDU P.C. board normal?
Is smoothing condenser normal?
(1500µF, 350V)
Correct power line.
Replace compressor.
Correct connection
of wire connector.
Check capacity coming-out/
external appearance.
Replace fuse and
IPDU P.C. board.
YES
YES
NO
YES
YES
NO
NO
YES
NO
NO