–28–
EN
F13 F13
01:Comp. 1 side
02:Comp. 2 side
03:Comp. 3 side
TH sensor error IPDU
F15 F15 Outdoor unit temp. sensor miscabling (TE, TL) I/F
F16 F16 Outdoor unit pressure sensor miscabling (Pd, Ps) I/F
F19 Hot water module TCJ2 (TF) sensor error Hot water module
F22 F22 TD3 sensor error I/F
F23 F23 Ps sensor error I/F
F24 F24 Pd sensor error I/F
F25 Hot water module TWI (TA) sensor error Hot water module
F26 Hot water module TWO (TC2) sensor error Hot water module
F29 Indoor unit other error Indoor unit
F31 F31 Indoor unit EEPROM error I/F
H01 H01
01:Comp. 1 side
02:Comp. 2 side
03:Comp. 3 side
Compressor break down IPDU
H02 H02
01:Comp. 1 side
02:Comp. 2 side
03:Comp. 3 side
Compressor trouble (lock) IPDU
H03 H03
01:Comp. 1 side
02:Comp. 2 side
03:Comp. 3 side
Current detect circuit system error IPDU
H04 H04 Comp. 1 case thermo operation I/F
H05 H05 TD1 sensor miswiring I/F
H06 H06 Low pressure protective operation I/F
H07 H07 Oil level down detective protection I/F
H08 H08
01:TK1 sensor error
02:TK2 sensor error
03:TK3 sensor error
04:TK4 sensor error
05:TK5 sensor error
Oil level detective temp sensor error I/F
H14 H14 Comp. 2 case thermo operation I/F
H15 H15 TD2 sensor miswiring I/F
H16 H16
01:TK1 oil circuit system error
02:TK2 oil circuit system error
03:TK3 oil circuit system error
04:TK4 oil circuit system error
05:TK5 oil circuit system error
Oil level detective circuit error I/F
H25 H25 TD3 sensor miswiring I/F
L02 Outdoor unit combination error Hot water module
L03 Indoor unit centre unit duplicated Indoor unit
L04 L04 Outdoor unit line address duplicated I/F
L05 Duplicated indoor units with priority (Displayed in indoor unit with priority) I/F
L06 L06 No. of indoor units with priority Duplicated indoor units with priority (Displayed in unit other than indoor unit with priority) I/F
L07 Group line in individual indoor unit Indoor unit
L08 L08 Indoor unit group / Address unset Indoor unit, I/F
L09 Indoor unit capacity unset Indoor unit
L10 L10 Outdoor unit capacity unset I/F
L17 Outdoor unit type mismatch error I/F
Check code
Check code name Judging device
Wired remote controller display
Outdoor unit 7-segment display