–28–
EN
F13 F13
01:Comp. 1 side
02:Comp. 2 side
03:Comp. 3 side
TH sensor error IPDU
F15 F15 — Outdoor unit temp. sensor miscabling (TE, TL) I/F
F16 F16 — Outdoor unit pressure sensor miscabling (Pd, Ps) I/F
F19 — — Hot water module TCJ2 (TF) sensor error Hot water module
F22 F22 — TD3 sensor error I/F
F23 F23 — Ps sensor error I/F
F24 F24 — Pd sensor error I/F
F25 — — Hot water module TWI (TA) sensor error Hot water module
F26 — — Hot water module TWO (TC2) sensor error Hot water module
F29 — — Indoor unit other error Indoor unit
F31 F31 — Indoor unit EEPROM error I/F
H01 H01
01:Comp. 1 side
02:Comp. 2 side
03:Comp. 3 side
Compressor break down IPDU
H02 H02
01:Comp. 1 side
02:Comp. 2 side
03:Comp. 3 side
Compressor trouble (lock) IPDU
H03 H03
01:Comp. 1 side
02:Comp. 2 side
03:Comp. 3 side
Current detect circuit system error IPDU
H04 H04 — Comp. 1 case thermo operation I/F
H05 H05 — TD1 sensor miswiring I/F
H06 H06 — Low pressure protective operation I/F
H07 H07 — Oil level down detective protection I/F
H08 H08
01:TK1 sensor error
02:TK2 sensor error
03:TK3 sensor error
04:TK4 sensor error
05:TK5 sensor error
Oil level detective temp sensor error I/F
H14 H14 — Comp. 2 case thermo operation I/F
H15 H15 — TD2 sensor miswiring I/F
H16 H16
01:TK1 oil circuit system error
02:TK2 oil circuit system error
03:TK3 oil circuit system error
04:TK4 oil circuit system error
05:TK5 oil circuit system error
Oil level detective circuit error I/F
H25 H25 — TD3 sensor miswiring I/F
L02 — — Outdoor unit combination error Hot water module
L03 — — Indoor unit centre unit duplicated Indoor unit
L04 L04 — Outdoor unit line address duplicated I/F
L05 — — Duplicated indoor units with priority (Displayed in indoor unit with priority) I/F
L06 L06 No. of indoor units with priority Duplicated indoor units with priority (Displayed in unit other than indoor unit with priority) I/F
L07 — — Group line in individual indoor unit Indoor unit
L08 L08 — Indoor unit group / Address unset Indoor unit, I/F
L09 — — Indoor unit capacity unset Indoor unit
L10 L10 — Outdoor unit capacity unset I/F
L17 — — Outdoor unit type mismatch error I/F
Check code
Check code name Judging device
Wired remote controller display
Outdoor unit 7-segment display
Auxiliary code
55-EN 56-EN
+00EH99897401-3_00Ta.book Page 28 Wednesday, May 11, 2016 3:36 PM