E6582051
- 5 -
Cautions for parameters
Warning
Prohibited
Do not use application of writing into same parameter more than 100,000 times.
The Life of EEPROM is approximately 100,000 times. Frequent writing to the EEPROM
of inverter will cause a memory corruption.
Notes on use
Notes
Do not install the inverter where the temperature or the humidity will change rapidly.
Keep a distance of 20cm or more between the inverter 's power cable and the data
transmission cable.
Or the inverter might malfunction because of noise.
Insert a magnetic contactor or similar device between the inverter and the power supply
to ensure that power is turned off if an emergency stop command is entered through the
network.

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS3 and is the answer not in the manual?

Toshiba TOSVERT VF-AS3 Specifications

General IconGeneral
ModelTOSVERT VF-AS3
CategoryInverter
Overload Capacity150% for 60 seconds
Cooling MethodForced Air Cooling
Control MethodV/f control, Sensorless vector control
Braking UnitBuilt-in
Communication ProtocolsModbus RTU, DeviceNet, Profibus DP
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Ground Fault
EnclosureIP20
Operating Temperature-10°C to +50°C
Humidity5-95% (non-condensing)
AltitudeUp to 1000m