- 16 -
3.2.
Wiring
This product is equipped with dual shielded RJ45 connectors. The shielding of RJ45 connectors are
connected to the grounding terminal of inverter.
When you use this product with VF-S15, please connect the grounding terminal of SBP009Z to grounding
terminal of inverter by attached grounding wire.
When you use this product with VF-AS3, you do not need the ground line wiring. Because when you attach
this product to VF-AS3, Shielded RJ45 connector is connected to the ground terminal of the inverter
Communication cable specifications
CAT 5e or more
Connector RJ45, non-crossover cable
Shielded twisted pair cable
Maximum cable length = 100 m (328 ft)
The following table describes the pin layout of RJ45 connecter.
Pin
Signal
1
TD+
2
TD-
3
RD+
4
-
5
-
6
RD-
7
-
8
-
* Fix a cable so that a communication connector may be not taken the weight of wire.
8………………1
Port L and Port R
Connect the grounding terminal by grounding wire.

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS3 and is the answer not in the manual?

Toshiba TOSVERT VF-AS3 Specifications

General IconGeneral
ModelTOSVERT VF-AS3
CategoryInverter
Overload Capacity150% for 60 seconds
Cooling MethodForced Air Cooling
Control MethodV/f control, Sensorless vector control
Braking UnitBuilt-in
Communication ProtocolsModbus RTU, DeviceNet, Profibus DP
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Ground Fault
EnclosureIP20
Operating Temperature-10°C to +50°C
Humidity5-95% (non-condensing)
AltitudeUp to 1000m

Related product manuals