E6582051
- 22 -
4.2.
Communication parameters for PROFINET
The following parameters can be used for cyclic transmission of this product.
The scanner input address (
c001
-
c006
) and the scanner output address (
c021
-
c026
) are
the monitor parameters. When using "Telegram 100", "Telegram 101" or "Telegram 102", configure the
scanner input / output with the network configuration tool of the PROFINET controller (PLC).
4.2.1. Relation parameters for VF-S15/MB1
Title
Communi
cation No.
Function Description
c001
C001 Scanner input 1 address
0: -
1:
fa06
(Communication command 1)
2:
fa23
(Communication command 2)
3:
fa07
(Frequency command, 0.01Hz)
5:
fa50
(Terminal output data)
6:
fa51
(FM analog output)
8:
f601
(Stall prevention level, %)
13:
acc
(Acceleration time 1, 0.1s) (*1)
14:
dec
(Deceleration time 1, 0.1s) (*1)
15:
ul
(Upper limit, 0.01Hz)
16:
vb
(Torque boost value 1, 0.1%)
17:
vlv
(Base frequency voltage 1, 0.1V)
c002
C002 Scanner input 2 address
0-17 (Same as
c001
)
c003
C003 Scanner input 3 address
0-17 (Same as
c001
)
c004
C004 Scanner input 4 address
0-17 (Same as
c001
)
c005
C005 Scanner input 5 address
0-17 (Same as
c001
)
c006
C006 Scanner input 6 address
0-17 (Same as
c001
)
c021
C021 Scanner output 1 address
0: -
1:
fd01
(Status information 1)
2:
fd00
(Output frequency, 0.01Hz)
3:
fd03
(Output current, 0.01%)
4:
fd05
(Output voltage, 0.01%)
5:
fc91
(Alarm information)
6:
fd22
(PID feedback value, 0.01Hz)
7:
fd06
(Input terminal status)
8:
fd07
(Output terminal status)
9:
fe36
(VIB input, 0.01%)
10:
fe35
(VIA input, 0.01%)
11:
fe37
(VIC input, 0.01%)
12:
fd04
(Input voltage (DC detection), 0.01%)
13:
fd16
(Estimated speed 0.01Hz)
14:
fd18
(Torque, 0.01%)
15 to 18: -
19:
f880
(Free notes)
20:
fd29
(Input power, 0.01kW)
21:
fd30
(Output power, 0.01kW)
22:
fe14
(Cumulative operation time, 1 hour)
23:
fe40
(FM terminal output monitor, 0.01%)
24: -
25:
fd20
(Torque current, 0.01%)
26:
fd23
(Motor overload factor, 0.01%)
27:
fd24
(Drive overload factor, 0.01%)
28:
fd25
(PBR overload factor, %)
29:
fd26
(Motor load factor, %)
30:
fd27
(Drive load factor, %)
31:
fe56
(Pulse train input, pps)
32:
fe70
(Drive rated current, 0.1A)
33:
fe76
(Input Watt-hour, 0.1kWh
10
f749
)
34:
fe77
(Output Watt-hour, 0.1kWh
10
f749
)
35:
fd83
(IGBT temperature, degree C)
c022
C022 Scanner output 2 address
0-35 (Same as
c021
)
c023
C023 Scanner output 3 address
0-35 (Same as
c021
)
c024
C024 Scanner output 4 address
0-35 (Same as
c021
)
c025
C025 Scanner output 5 address
0-35 (Same as
c021
)
c026
C026 Scanner output 6 address
0-35 (Same as
c021
)
(*1): The unit depends on
f519
setting