E6582051
- 62 -
8.5. "06 (0x06) Write Single Register" function
This Modbus request is used to write the value to the inverter parameter.
Request format:
Byte Meaning
0 Function Code = 06h
1 Communication No. of Parameter Hi
2 Communication No. of Parameter Lo
3 Write Data Hi
4 Write Data Lo
Response format:
Byte Meaning
0 Function Code = 06h
1 Communication No. of Parameter Hi
2 Communication No. of Parameter Lo
3 Write Data Hi
4 Write Data Lo
Exception response format:
Byte Meaning
0 Function Code = 86h
1
Exception Code
01: Illegal Function
02: Illegal Data Address
03: Illegal Data Value
04: Slave Device Failure
Notes
When you use this Modbus request, the value is written to the EEPROM.

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS3 and is the answer not in the manual?

Toshiba TOSVERT VF-AS3 Specifications

General IconGeneral
ModelTOSVERT VF-AS3
CategoryInverter
Overload Capacity150% for 60 seconds
Cooling MethodForced Air Cooling
Control MethodV/f control, Sensorless vector control
Braking UnitBuilt-in
Communication ProtocolsModbus RTU, DeviceNet, Profibus DP
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Ground Fault
EnclosureIP20
Operating Temperature-10°C to +50°C
Humidity5-95% (non-condensing)
AltitudeUp to 1000m