E6582051
- 51 -
6.6.
Access to the PROFIdrive parameter
In the cyclic PROFINET communication, the parameter data is transferred via Telegram 100 or 101. If the
requirement is not executed, the cause is distinguished by octet 7 and 8.
PKW
(Parameter ID/value)
PZD
Process data (cyclically)
PKE IND PWE
PZD1
STW
ZSW
PZD2
HSW
HIW
Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 Octet 6 Octet 7 Octet 8
PKE (Parameter ID)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
AK (Request from Master to this product
Request ID Function Note
0 No task
1 Request parameter value for PNU access
2 Change parameter value (word) for PNU access
6 Request parameter value (array) for PNU access or inverter parameter access
7 Change parameter value (array) for PNU access or inverter parameter access
AK (Response from this product to Master)
Response ID Function
0 No response
1 Transfer parameter value (word)
4 Transfer parameter value (array)
7 Task can not be executed, followed by error number
0 = Illegal parameter number
1 = Parameter value cannot be changed
2 = Lower or upper limit violated
3 = Erroneous sub index
11 = No parameter change rights
17 = Task cannot be executed due to operating status
(e.g. parameter is currently read-only)
18 = Other error
102 = Request not supported
SPM: always 0.
AK
(Task ID/Response ID)
PNU
(Parameter number)
SPM

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS3 and is the answer not in the manual?

Toshiba TOSVERT VF-AS3 Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-AS3
CategoryInverter
LanguageEnglish

Related product manuals