END USER SETTINGS - DEHUMIDITY
DEFINITION DEPENDENCIES FUNCTION
The Humidity Screen is used to allow the end
user access to change or view humidify and
dehumidify set points on the thermostat. The
orange Hum Setpoint Wheel is used to adjust
the humidify set point. The blue Dehum Set
point Wheel is used to adjust the cool to
dehumidify set point.
If cooling equipment is not available
(based on the Outdoor Equipment Type
selections made in section 4.8.3) then
the COOL TO DEHUMIDIFY
functionality is not available in the
thermostat and the blue Dehum Set
point Wheel will be “greyed” and its
functionality will be disabled (as shown
in the rightmost screen above).
The cool to dehumidify
function tells the system to
operate the compressor,
within limits, when there is a
dehumidification demand
even if there is no cooling
demand. The limits are that
the system may overcool up
to 3° F (1.7° C), but no more,
while attempting to satisfy a
dehumidification demand.