17
SENSORS
Compressor Dome Temperature
This table shows the corresponding voltage, resistance
and temperature readings for the Dome Temperature
Sensor when measured across pins 1 and 10. The
power source for the Dome Temperature Sensor is
3.2VDC.
7(03 ) 7(03 &
7+(50,6725
5(6,67$1&(
2+06
92/76 '&
3,1 72 3,1
7(03 ) 7(03 &
7+(50,6725
5(6,67$1&(
2+06
92/76 '&
3,1 72 3,1
Figure 6. Dome Temperature Sensor
Pin 1 & 10 (Red)
Integrated Variable Speed Control Board
J1
123456789
101112131415161718
A working Compressor Dome Temperature Sensor is
required for:
• Protection (High/Low Temperature)
• Preheating (Sump Heat)
• Outdoor EEV Control
• Diagnostics; Reverse rotation, Flooding, Charge
Level
The Dome Temperature Sensor control contains an
NTC thermistor input for sensing the Compressor
Dome Temperature. The thermistor has a nominal
resistance of § 10k ohms at 75°F. The minimum range
required for the Dome Temperature input is —31°F to
302°F. when measured across pins 1 and 10.
NNoottee:: Secure Installation of Dome Sensor is required
for reliable compressor & system operation.