20
18-BC89D1-1D-EN
Start Up
1. Ensure you have completed the following sections. ”Refrigerant Line Brazing, p. 12 through ”Electrical High Voltage, p. 18
2. Set System Thermostat to OFF.
3. Turn on disconnect(s) to apply power to the indoor and outdoor
units.
ON
OFF
4. Wait 3 hours before starting the unit if the outdoor ambient
temperature is below 85° F.
3 HRS.
5. Run the system using the “Charging Mode-Cooling” test mode
found in the 850/950 comfort control. This is the only approved
method for setting the system charge level by subcooling.
Follow the on-screen prompts.