11 2 CLCH-SVX07C-EN
Start-Up
Table 30. Side inlet low-flow Traq dampers - diagonal economizer section - VCM voltage versus airflow at sea level
Unit size Part number
Traq damper
size (in) Quantity
Peak velocity
(fpm)
Total area
(ft2)
CFM@10VD
C peak
velocity
L/s@10VDC
peak
velocity Unit size
4
50182901 13
Min. Outside Air 1
2475
0.92 2279 1076
Economizing 1 0.92 2279 1076
6
Min. Outside Air 1 0.92 2279 1076
Economizing 1 0.92 2279 1076
8
Min. Outside Air 1 0.92 2279 1076
Economizing 1 0.92 2279 1076
10
50182902 16
Min. Outside Air 1
2475
1.40 3455 1630
Economizing 1 1.40 3455 1630
12
Min. Outside Air 1 1.40 3455 1630
Economizing 1 1.40 3455 1630
14
Min. Outside Air 1 1.40 3455 1630
Economizing 1 1.40 3455 1630
17 50182901 13
Min. Outside Air 1
2475
0.92 2279 1076
Economizing 3 2.76 6838 3227
21 50182924 20
Min. Outside Air 1
2600
2.18 5671 2676
Economizing 1 2.18 5671 2676
25 50182902 16
Min. Outside Air 1
2600
1.40 3630 1713
Economizing 3 4.19 10889 5138
30 50182924 20
Min. Outside Air 1
2600
2.18 5671 2676
Economizing 2 4.36 11341 5352
35
50182904 28
Min. Outside Air 1
2600
4.27 11112 5244
Economizing 1 4.27 11112 5244
40
Min. Outside Air 1 4.27 11112 5244
Economizing 1 4.27 11112 5244
50 50182903 24
Min. Outside Air 1
2600
3.14 8164 3853
Economizing 2 6.28 16328 7705
57 50182903 24
Min. Outside Air 1
2600
3.14 8164 3853
Economizing 3 9.42 24492 11558
66 50182904 28
Min. Outside Air 1
2600
4.27 11112 5244
Economizing 2 8.55 22224 10488
80 50182904 28
Min. Outside Air 1
2600
4.27 11112 5244
Economizing 3 12.82 33336 15731
100
50182904 28
Min. Outside Air 1
2600
4.27 11112 5244
Economizing 4 17.10 44448 20975
120
Min. Outside Air 1 4.27 11112 5244
Economizing 4 17.10 44448 20975