Installation
13CG-SVX06D-E4
Unit nameplate
The unit nameplate gives the
complete model reference numbers.
The unit power rating is shown, and
power supplies should not deviate by
more than 5% from the rated power.
Compressor motor amperage is
shown in box I.MAX. The customer's
electrical installation must be able to
withstand this current.
Installation instructions
Foundations
No special foundations are required,
provided the supporting surface is
flat and level, and can withstand the
weight or the unit.
Isolating rubber pads
6 pads are supplied as standard with
the machine (55x150mm). They
should be placed between the
supporting floor and the unit to
isolate from the ground. Trane does
not recommend to install spring
isolators.
Water drain hole
Install a drain hole wide enough to
drain away water from the unit in the
event of shut-down or repair.
Clearance
Respect recommended clearance
around the unit to allow maintenance
operation to take place without
obstruction. For minimum clearance,
consult the certified submittals,
which are available on request from
your Trane Agency.