Operation
55CG-SVX06D-E4
Seasonal start-up
Check water flows and interlocks.
Check Ethylene glycol
concentration in the chilled water
circuit if glycol presence is
required
Check operational set points and
performance
Calibrate controls
Check operation of all safety
devices
Inspect contacts and tighten
terminals
Megger the motor compressor
windings
Record operating pressures,
temperatures, amperages and
voltage
Carry out leak test
Check configuration of unit
control module
Change the oil as required based
upon results of the oil analysis
made during seasonal shutdown.
Get the 8 condition measurements at
the same time, on each circuit.
•HP
•LP
Suction temperature
Discharge temperature
Liquid temperature
Water entering temperature
Water leaving temperature
Outdoor ambient temperature
Then calculate the sub-cooling and
superheat. No diagnosis can be
accurate with one of these records
missing.
Check operation of
machines/compare conditions of
operation against original
commissioning data.
Fill out the visit log sheet and
review with the operator