Operation
CG-SVX06D-E454
Control and unit operation
The control is through the
TRACER CH530 control module.
Check the chilled water pump(s)
operate(s)
Start up the unit following
procedure described in the
CGWN-CCUN User Manual. The
unit will operate correctly when
there is sufficient water flow. The
compressors will start up if the
evaporator water leaving
temperature is above the control
module setpoint.
Weekly start up
Check the chilled water pump(s)
operates
Start up the unit following
procedure described in the User
Guide.
Weekend shutdown
If the unit needs to be shut down
for a short period of time, stop the
unit following procedure
described in the CGWN-CCUN
User Manual (See "Clock" menu)
If the unit is shut down for a
longer period, see under
"Seasonal shutdown", below.
Ensure that all safety precautions
are taken to prevent frost
damages during negative ambient
temperature.
Do not put the general disconnect
switches to off, except if the unit
is drained.
Trane does not recommend draining
the unit, due to the fact that it
increases tube corrosion.
Seasonal shutdown
Check water flows and interlocks.
Check glycol concentration in the
chilled water circuit if glycol
presence is required
Carry out leak test.
Carry out oil analysis
Record operating pressures,
temperatures, amperages and
voltage.
Check operation of
machines/compare conditions of
operation against original
commissioning data.
Stop the unit following procedure
described in the CGWN-CCUN
User Manual.
Ensure that all safety precautions
are taken to prevent frost
damages during negative ambient
temperature.
Fill out the visit log sheet and
review with the operator
Do not put the general disconnect
switch to off, except if the unit is
drained.
Trane does not recommend draining
the unit, due to the fact that it
increases tube corrosion.