Installation
29CG-SVX06D-E4
Table 12 - Recommended discharge line diameters for horizontal risers (Circuit 1)
Table 13 - Recommended discharge line diameters for horizontal risers (Circuit 2)
Required discharge pipe diameter - Circuit 2
Unit size -12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14
CCUN 205 7/8" 1"1/8 1"3/8
CCUN 206 7/8" 1"1/8 1"3/8
CCUN 207 7/8" 1"1/8 1"3/8
CCUN 208 1"1/8 1"3/8 1"5/8
CCUN 209 1"1/8 1"3/8 1"5/8
CCUN 210 1"1/8 1"3/8 1"5/8
CCUN 211 1"1/8 1"3/8 1"5/8
CCUN 212 1"3/8 1"5/8 2"1/8
CCUN 213 1"5/8 2"1/8
CCUN 214 1"5/8 2"1/8
CCUN 215 1"5/8 2"1/8 2"5/8
Required discharge pipe diameter - Circuit 1
Unit size -12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14
CCUN 205 7/8" 1"1/8 1"3/8
CCUN 206 7/8" 1"1/8 1"3/8
CCUN 207 7/8" 1"1/8 1"3/8
CCUN 208 1"1/8 1"3/8 1"5/8
CCUN 209 1"1/8 1"3/8 1"5/8
CCUN 210 1"1/8 1"3/8 1"5/8
CCUN 211 1"1/8 1"3/8 1"5/8
CCUN 212 1"5/8 2"1/8
CCUN 213 1"5/8 2"1/8
CCUN 214 1"5/8 2"1/8 2"5/8
CCUN 215 1"5/8 2"1/8 2"5/8