CLCH-PRC03C-EN 13
Dimensions and Weights
Service Clearances
Figure 1. Service Clearance
Table 1. Service clearances (inches)
Clearance Items 3 6 8 10 12 14 17 21 25 30 35 40 50 57 66 80 100 120
A (filter) 484848484848484848484848484852565858
B (coil) 48 60 64 75 79 83 89 91 93 106 110 123 134 134 150 150 165 165
C (fan) 48484851545861606666657077779391101101
D (starter or VFD) 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60
Note: At a minimum, the above clearance dimensions are recommended on one side of the unit for regular service and maintenance. Refer to as-built
submittal for locations of items such as filter access doors, coil, piping connections, motor locations, etc. Sufficient clearance must be provided on
all sides of unit for removal of panels or module-to-module attachment brackets. Clearance for starters, VFDs, or other high-voltage devices must
be provided per NEC requirements.